5motor control (mctrl) – Lenze 8400 motec User Manual

Page 83

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

83

5

Motor control (MCTRL)

5.2

Motor selection/Motor data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Motor data
In the parameterisation dialog, the data of the motor nameplate for the selected motor are

displayed under "Motor data".

Actual values
When an online connection to the controller has been established, the following actual values are

displayed in the parameterisation dialog under "Actual values":

Note!

Sensorless vector control in particular requires the motor data parameters to be set. The

motor data comprise the data of the motor nameplate and the data of the motor

equivalent circuit.
If the motor has been selected via the motor catalogue of the »Engineer« or the motor

data have been adapted offline using the »Engineer«, all motor data must then be

copied to the controller and saved power-failure-proof to the memory module (device

command:

C00002/11

) when an online connection has been established.

Parameter

Info

C00081

Rated motor power

C00087

Rated motor speed

C00088

Rated motor current

C00089

Rated motor frequency

C00090

Rated motor voltage

C00091

Motor cos ϕ

Parameter

Info

C00051

Actual speed value

C00052

Motor voltage

C00053

DC-bus voltage

C00054

Motor current

C00066

Thermal motor load (I2xt)

Highlighted in grey = display parameter

Advertising