_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Selection of the main speed setpoint
The main speed setpoint is selected in the Lenze setting via the analog input 1.

• Scaling: 10 V ≡ 100 % reference speed (

C00011

)

• The main setpoint is transformed to a speed setpoint in the setpoint encoder via a ramp

function generator with linear or S-shaped ramps.

• For a detailed functional description see FB

L_NSet_1

.

( 443)

Motor potentiometer function
Alternatively, the main speed setpoint can be generated via a motor potentiometer function.

• In the Lenze setting, the motor potentiometer function is deactivated.
• Activation is possible via

C00806

or via the bMPotEnable input.

• The behaviour of the motor potentiometer during switch-on of the drive system can be selected

in

C00805

.

• For a detailed functional description see FB

L_MPot_1

.

( 439)

Process controller
A process controller (PID controller) is connected downstream of the setpoint generator.

• In the Lenze setting, the process controller is deactivated.
• The activation is executed by selecting the operating mode in

C00242

.

• For a detailed functional description see FB

L_PCTRL_1

.

( 450)

nAdapt_a

(

C00830/7

)

Adaptation of gain Vp set in

C00222

in percent

nAct_a

(

C00830/6

)

Speed or actual sensor value (actual process value)

nInflu_a

(

C00830/9

)

Limitation of the influencing factor in percent

Speed setpoint

(

C00050

)

Speed setpoint