6 enabling controller and selecting speed, Enabling controller and selecting speed, 3commissioning – Lenze 8400 motec User Manual

Page 41

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

41

3

Commissioning

3.5

Commissioning of the "Actuating drive speed" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.5.5

Saving parameter settings safe against mains failure

The parameter set must be saved to the device safe against mains failure to prevent parameter

settings becoming lost due to mains switching.

Saving parameter set

3.5.6

Enabling controller and selecting speed

If the controller is in the "

SwitchedOn

" status:

1. Enable controller: Set terminal RFR to HIGH level.
2. Select speed:

• In the "Terminals 0" by selecting a voltage at the analog input or by selecting a fixed setpoint

via the digital inputs DI1/DI2.

Stop!

Before stipulating a speed setpoint, check whether the brake in the form of a holding

brake on the motor shaft has been released!

Note!

If the controller is enabled and the "Inhibit at power-on" auto-start option is activated in

C00142

(Lenze setting) when the mains is connected, the controller remains in the

"

ReadyToSwitchOn

" state.

In order to change to the "

SwitchedOn

" status, the controller enable must first be

cancelled: Set terminal RFR to LOW level.

DI1

DI2

Speed selection

LOW

LOW

The main speed setpoint is selected via the analog input 1

• Scaling: 10 V ≡ 100 % reference speed (

C00011

)

HIGH

LOW

The fixed setpoint 1 (

C00039/1

) is used as main speed setpoint.

• Lenze setting: 40 % of the reference speed (

C00011

)

LOW

HIGH

The fixed setpoint 2 (

C00039/2

) is used as main speed setpoint.

• Lenze setting: 60 % of the reference speed (

C00011

)

HIGH

HIGH

The fixed setpoint 3 (

C00039/3

) is used as main speed setpoint.

• Lenze setting: 80 % of the reference speed (

C00011

)

Note!

Observe the actual speed value (display in

C00051

) and the

LED status display

at the

controller.