Commissioning

3.6

Commissioning of the "Switch-off positioning" technology application

50

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.6.5

Saving parameter settings safe against mains failure

The parameter set must be saved to the device safe against mains failure to prevent parameter

settings becoming lost due to mains switching.

Save parameter set.

3.6.6

Enable controller and test application

If the controller is in the "

SwitchedOn

" status:

1. Enable controller: Set terminal RFR to HIGH level.
2. Select the respective control signals via the digital inputs.

Stop!

Before stipulating a speed setpoint, check whether the brake in the form of a holding

brake on the motor shaft has been released!

Note!

If the controller is enabled and the "Inhibit at power-on" auto-start option is activated in

C00142

(Lenze setting) when the mains is connected, the controller remains in the

"

ReadyToSwitchOn

" state.

In order to change to the "

SwitchedOn

" status, the controller enable must first be

cancelled: Set terminal RFR to LOW level.

Note!

Observe the actual speed value (display in

C00051

) and the

LED status display

at the

controller.