Device control (DCTRL)

4.1

Device commands (C00002/x)

68

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.1.11

Device search function

This function extension is only available from version 04.00.00!

In some applications where controllers are positioned in a spacious plant, it is often difficult to lo-

cate a device connected online for e.g. maintenance work. There is an established online connection

with the device but you do not know where the controller is located physically.
The

C00002/27

= "1: On / start" device command serves to carry out an "optical location":

• For the time set in

C00181/1

, the LED display at the front of the device flashes. Afterwards, the

function is turned off automatically.

• If the device command is executed again within the set time period, the duration is extended

accordingly.

• The setting

C00002/27

= "0: Off / ready" serves to abort or switch off the function.

• Adjustable time period: 0 ... 6000 s (Lenze setting: 5 s)

Tip!

The device search function can also be activated via the

toolbar icon.