Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00175

C00177

C00178

C00179

Parameter | Name:

C00175 | Brake energy management: Selection of the braking procedure

Data type: UNSIGNED_8

Index: 24400

d

= 5F50

h

Selection of the braking procedure

Select response if the brake resistor is controlled

Selection list

(Lenze setting printed in bold)

Info

0 Brake resistor

The brake resistor is used. The external brake resistor is

triggered via a hardware circuit. The DC-bus voltage has

no influence on the brake ramp.

2 Brake resistor and stop of the ramp

function generator

The brake resistor and the "Ramp function generator

stop" signal are used. If the brake chopper threshold is

exceeded, the ramp function generator is stopped.

4 Brake resistor and motor brake and

ramp stop

From version 02.00.00

The brake resistor as well as the "Ramp function

generator stop" signal and the "Inverter motor brake"

function are used.

6 Brake resistor and motor

From version 02.00.00

The brake resistor is used. The braking energy is

degraded by overmagnetising the motor by the

percentage value set in

C00984

.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00177 | Switching cycles

Data type: UNSIGNED_32

Index: 24398

d

= 5F4E

h

Counter of different switching cycles and stressful situations
Display range

(min. value | unit | max. value)

0

2147483647

Subcodes

Info

C00177/1

Number of mains switching cycles

C00177/2

Number of switching cycles of the output relay

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00178 | Elapsed-hour meter

Data type: UNSIGNED_32

Index: 24397

d

= 5F4D

h

Display of operating hours in seconds
Display range

(min. value | unit | max. value)

0

s

2147483647

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00179 | Power-on time meter

Data type: UNSIGNED_32

Index: 24396

d

= 5F4C

h

Display of the power-on time in seconds
Display range

(min. value | unit | max. value)

0

s

2147483647

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1