Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

295

9

Diagnostics & error management

9.7

Maloperation of the drive

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Motor rotates irregu-

larly

Motor cable is defective

Check motor cable

Maximum motor current in motor or genera-

tor mode is set too low

Adjust settings to the application:

C00022:

Imax in motor mode

C00023

: Imax in generator mode

Motor is underexcited or overexcited

Check parameterisation:

C00006

: Motor control

C00015

: VFC: V/f base frequency

C00016

: VFC: Vmin boost

Rated motor data (stator resistance, speed,

current, frequency, voltage) and cos ϕ and/

or magnetising inductance is not adapted to

the motor data

Execute automatic motor parameter identifi-

cation with the

C00002/23

device command

- or -

Adjust motor parameters manually:

C00084

: Motor stator resistance

C00087

: Rated motor speed

C00088

: Rated motor current

C00089

: Rated motor frequency

C00090

: Rated motor voltage

C00091

: Motor cosine phi

C00092

: Motor magnetising inductance

Motor windings are wired incorrectly

Reverse from star connection to delta con-

nection

Motor consumes too

much current

V

min

boost has been selected too high

Correct setting with

C00016

V/f base frequency has been selected too low Correct setting with

C00015

Rated motor data (stator resistance, speed,

current, frequency, voltage) and cos ϕ and/

or magnetising inductance is not adapted to

the motor data

Execute automatic motor parameter identifi-

cation with the

C00002/23

device command

- or -

Adjust motor parameters manually:

C00084

: Motor stator resistance

C00087

: Rated motor speed

C00088

: Rated motor current

C00089

: Rated motor frequency

C00090

: Rated motor voltage

C00091

: Motor cosine phi

C00092

: Motor magnetising inductance

Motor parameter

identification is

aborted with error

LP1

Motor is too small compared to the rated de-

vice power (>1 : 3)

Use device with lower rated power

DC-injection braking (DCB) is active via ter-

minal

Deactivate

DC-injection braking

Drive behaviour with

vector control is not

satisfactory

different

Optimise or manually adapt vector control

Sensorless vector control (SLVC)

Execute automatic motor parameter identifi-

cation with the

C00002/23

device command

Automatic motor data identification

Torque dip in field

weakening range

or

motor stalling when

being operated in the

field weakening

range

Motor is overloaded

Check motor load

Motor windings are wired incorrectly

Reverse from star connection to delta con-

nection

V/f base frequency is set too high

Correct setting with

C00015

Mains voltage too low

Increase mains voltage

Parameter changes

are not accepted

Settings according to DIP1, DIP2, P1, P2 and

P3 are active (local mode)

Set DIP1/switch 1 to "OFF" in order that no

parameters of the memory module are over-

written when the device is started.

• See display parameters

C01911

and

C01912

for details.

Maloperation

Cause

Remedy