Parameter | Name:
C00013 | Decel. time - main setpoint
Data type: UNSIGNED_32
Index: 24562
d
= 5FF2
h
FB: Deceleration time of the ramp generator for the main speed setpoint
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9 2.0 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00015 | VFC: V/f base frequency
Data type: UNSIGNED_16
Index: 24560
d
= 5FF0
h
V/f base frequency for V/f characteristic control (
) and V/f control (
)
• The motor voltage increases linearly with the frequency until the base frequency is reached. From this value on,
the motor voltage remains constant, the speed increases and the maximum torque decreases.
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
7.5
Hz
999.9 50.0 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00016 | VFC: Vmin boost
Data type: UNSIGNED_16
Index: 24559
d
= 5FEF
h
Boost of the V/f voltage characteristic in the range of small speeds or frequencies with V/f characteristic control
(
) and V/f control (
)
• This may increase the starting torque.
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
100.0 0.0 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00018 | Switching frequency
Data type: UNSIGNED_8
Index: 24557
d
= 5FED
h
Selection of the pulse width modulated switching frequency transferred from the inverter to the motor
• When a variable switching frequency is selected, the switching frequency may change as a function of the load
and rotational frequency.
Selection of switching frequency
Selection list
(Lenze setting printed in bold)
2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised
23 16 kHz var/8 kHz min
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1