Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

337

11

Parameter reference

11.2

Parameter list | C00013

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00013

C00015

C00016

C00018

Parameter | Name:

C00013 | Decel. time - main setpoint

Data type: UNSIGNED_32

Index: 24562

d

= 5FF2

h

The

L_NSet_1

FB: Deceleration time of the ramp generator for the main speed setpoint

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 2.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00015 | VFC: V/f base frequency

Data type: UNSIGNED_16

Index: 24560

d

= 5FF0

h

V/f base frequency for V/f characteristic control (

VFCplus

) and V/f control (

VFCplus+encoder

)

• The motor voltage increases linearly with the frequency until the base frequency is reached. From this value on,

the motor voltage remains constant, the speed increases and the maximum torque decreases.

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.

Setting range

(min. value | unit | max. value)

Lenze setting

7.5

Hz

999.9 50.0 Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00016 | VFC: Vmin boost

Data type: UNSIGNED_16

Index: 24559

d

= 5FEF

h

Boost of the V/f voltage characteristic in the range of small speeds or frequencies with V/f characteristic control

(

VFCplus

) and V/f control (

VFCplus+encoder

)

• This may increase the starting torque.

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.

Motor control (MCTRL)

:

Setting the Vmin boost

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

100.0 0.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00018 | Switching frequency

Data type: UNSIGNED_8

Index: 24557

d

= 5FED

h

Selection of the pulse width modulated switching frequency transferred from the inverter to the motor

• When a variable switching frequency is selected, the switching frequency may change as a function of the load

and rotational frequency.

Selection of switching frequency

Selection list

(Lenze setting printed in bold)

2 8 kHz var./drive-optimised
3 16 kHz var./drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised

23 16 kHz var/8 kHz min

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1