C00990

C00991

C00992

C00994

Parameter | Name:

C00990 | Flying restart fct.: Activation

Data type: UNSIGNED_8

Index: 23585

d

= 5C21

h

Switch on/activate flying restart circuit for non-feedback drive systems

Flying restart fct.

Selection list

(Lenze setting printed in bold)

0 Off
1 On

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00991 | Flying restart fct.: Process

Data type: UNSIGNED_16

Index: 23584

d

= 5C20

h

Selection of the speed search range for the flying restart function

Flying restart fct.

Selection list

(Lenze setting printed in bold)

5 -n...+n | Last output frequency
6 -n...+n | Actual setpoint frequency

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00992 | Flying restart fct.: Start frequency

Data type: INTEGER_16

Index: 23583

d

= 5C1F

h

Manual selection of the starting value for the flying restart function

• Only active if

C00991

= 4 (cannot be selected yet for 8400 motec)

Flying restart fct.

Setting range

(min. value | unit | max. value)

Lenze setting

-200

Hz

200 10 Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00994 | Flying restart fct.: Current

Data type: INTEGER_16

Index: 23581

d

= 5C1D

h

Current to be injected during the flying restart process

• 100 % ≡ rated motor current (

C00088

).

• The flying restart current should amount to 10 ... 25 % of the rated motor current.

Flying restart fct.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

100.0 25.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100