6i/o terminals – Lenze 8400 motec User Manual

Page 198

Advertising
background image

6

I/O terminals

6.4

Electrical data

198

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Analog terminals

Terminal

Application / electrical data

AU/AI

Voltage or current input
General data:

Resolution: 10 bits

(Error: 1 digit ≡ 0.1 %, in relation to the final value)

Conversion rate: 1 kHz

In order to filter short-time faults in the analog signal char-

acteristic, the analog input value is led via a digital lag filter

with a time constant of 5 ms.

Processing cycle: 1 kHz (1 ms)

Electric strength of external voltage ±15 V, permanent

Temperature influence: ±0.5 % or ±1 mV/K

(T

amb

= -10 °C ... +55 °C)

When being configured as voltage input (

C00034

= "0")

Level/scaling: 0 ... +10 V ≡ 0 ... +2

14

≡ 0 ... +16384 ≡ 0 ... +100 %

Input resistance: > 80 kΩ

Input voltage in case of open circuit: Display 0 (U < 0.2 V, abs.)

Accuracy: ±0.1 V

Limit frequency: 315 Hz at -3 dB

When being configured as current input (

C00034

= "1" or "2")

Level/scaling: When

C00034

= "1":

0 ... +20 mA ≡ 0 ... +2

14

≡ 0 ... +16384 ≡ 0 ... +100 %

When

C00034

= "2" (life-zero):

+4 ... +20 mA ≡ 0 ... +2

14

≡ 0 ... +16384 ≡ 0 ... +100 %

Switching hysteresis: 1 % (at 20 mA)

Input resistance: approx. 250 Ω

Input voltage in case of open circuit: Display 0 (I < 0.1 mA)

Accuracy: ±0.1 mA

AR

10-V reference voltage

Output current: max. 10 mA

GA

Reference potential (analog ground, GND)