Diagnostics & error management

9.8

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oH3: Motor temperature triggered [xx.0119.00015]

oC5: Ixt overload [xx.0119.00050]

oC9: Ixt overload - shutdown limit [xx.0119.00052]

oC7: Motor overcurrent [xx.0123.00007]

Response (Lenze setting printed in bold)

Setting:

C00585

( Adjustable response)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The motor temperature monitoring mode at plug X??

has triggered.

Possible causes:

• The motor is overheated so that the thermal contact

integrated into the motor has been switched.

• An open circuit or a loose contact at the connections

mentioned above has occurred.

• Check motor temperature monitoring.

• Provide for sufficient cooling of the motor.

• Check terminals for open circuit or loose contact.

Response (Lenze setting printed in bold)

Setting:

C00604

( Adjustable response)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The Ixt overload check has tripped.

• Operating threshold = 100 % Ixt (adjustable in

C00123

)

Possible causes:

• Wrong dimensioning of the device with regard to its

motor load.

• Load cycles are not complied with.

• Check and, if required, correct dimensioning of the

device and the motor load with regard to technical

data.

• Reduce motor load cycles (observe load cycles accord-

ing to documentation).

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The Ixt overload check has tripped.

• Operating threshold = 110 % Ixt (fixed)

Possible causes:

• Wrong dimensioning of the device with regard to its

motor load.

• Load cycles are not complied with.

• Check and, if required, correct dimensioning of the

device and the motor load with regard to technical

data.

• Reduce motor load cycles (observe load cycles accord-

ing to documentation).

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Maximum current monitoring has tripped.

Check and, if required, correct dimensioning of the load

with regard to the installed device power.