Ps04: par. set device incompatible [xx.0144.00004, Ps31: ident. error [xx.0144.00031, Df01: internal error 01 [xx.0145.00001 – Lenze 8400 motec User Manual

Page 313: Df02: internal error 02 [xx.0145.00002, Df03: internal error 03 [xx.0145.00003, Xx.0145.00001, Xx.0145.00002, Xx.0145.00003, Xx.0144.00004, Xx.0144.00031

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

313

9

Diagnostics & error management

9.8

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

PS04: Par. set device incompatible [xx.0144.00004]

PS31: Ident. error [xx.0144.00031]

dF01: Internal error 01 [xx.0145.00001]

dF02: Internal error 02 [xx.0145.00002]

dF03: Internal error 03 [xx.0145.00003]

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The parameter set saved to the memory module is in-

compatible to the standard device.

• Incompatibility of the parameter set is e.g. caused if

the parameter set in the memory module has a higher

version than the standard device.

When the memory modules are exchanged, observe the

downward compatibility:

• OK: motec V1.0 to motec > V1.0

• Not OK: motec V2.0 to motec < V2.0

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Incompatible or unknown HW components have been

found.

• Check which HW components are faulty (

C00203/x

:

Product type code).

• Check connection between communication unit and

drive unit regarding for contact problems.

• Check temperature range of the device at the start.

• Replace communication unit.

• Check whether a software update at Lenze is possible.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Device error

• Reduce switching frequency (

C00018

) to 4 kHz.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Device error

• Mains switching or restart of the controller, respec-

tively.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Device error

• Mains switching or restart of the controller, respec-

tively.

• Please contact Lenze if the problem occurs again.

Advertising