Parameter reference

11.2

Parameter list | C00010

336

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00010

C00011

C00012

41 Network(ASi)

From version 04.00.00

The technology application is controlled via the "AS-i

Option" Communication Unit

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00007 | Control mode

Data type: UNSIGNED_16

Index: 24568

d

= 5FF8

h

Parameter | Name:

C00010 | Minimum analog setpoint

Data type: INTEGER_16

Index: 24565

d

= 5FF5

h

Lower limit for analog input

Note:

• Not effective with bipolar analog input (-10 V ... +10 V).

• With an offset (

C00026/1

) not equal to "0.0 %" or a gain (

C00027/1

) lower than "0.0 %", the minimum output

value (for the application) can fall below the value set here.

Analog terminals

Setting range

(min. value | unit | max. value)

0.0

%

100.0

Subcodes

Lenze setting

Info

C00010/1

0.0 %

Min. analog setpoint

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00011 | Appl.: Reference speed

Data type: UNSIGNED_16

Index: 24564

d

= 5FF4

h

Setting the reference speed

• In the controller, all speed-related signals are processed to one reference variable in percent.

• Set a reference speed here that corresponds to 100 %.

• The frequency that corresponds to the set reference speed is displayed in

C00059

.

Note:

This is not a maximum limitation!

All values in percent in the controller may be in a range of 0 ... 199.99 %.
Setting range

(min. value | unit | max. value)

Lenze setting

50

rpm

9999 1500 rpm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00012 | Accel. time - main setpoint

Data type: UNSIGNED_32

Index: 24563

d

= 5FF3

h

The

L_NSet_1

FB: Acceleration time of the ramp generator for the main speed setpoint

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 2.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000