C00010 | minimum analog setpoint, C00011 | appl.: reference speed, C00012 | accel. time - main setpoint – Lenze 8400 motec User Manual
Page 336: C00011, C00012, C00012), Rence speed set in, The reference speed, Up to the traversing speed set in, Nce speed in
11
Parameter reference
11.2
Parameter list | C00010
336
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00010
C00011
C00012
41 Network(ASi)
From version 04.00.00
The technology application is controlled via the "AS-i
Option" Communication Unit
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00007 | Control mode
Data type: UNSIGNED_16
Index: 24568
d
= 5FF8
h
Parameter | Name:
C00010 | Minimum analog setpoint
Data type: INTEGER_16
Index: 24565
d
= 5FF5
h
Lower limit for analog input
Note:
• Not effective with bipolar analog input (-10 V ... +10 V).
• With an offset (
) not equal to "0.0 %" or a gain (
) lower than "0.0 %", the minimum output
value (for the application) can fall below the value set here.
Setting range
(min. value | unit | max. value)
0.0
%
100.0
Subcodes
Lenze setting
Info
C00010/1
0.0 %
Min. analog setpoint
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00011 | Appl.: Reference speed
Data type: UNSIGNED_16
Index: 24564
d
= 5FF4
h
Setting the reference speed
• In the controller, all speed-related signals are processed to one reference variable in percent.
• Set a reference speed here that corresponds to 100 %.
• The frequency that corresponds to the set reference speed is displayed in
Note:
This is not a maximum limitation!
All values in percent in the controller may be in a range of 0 ... 199.99 %.
Setting range
(min. value | unit | max. value)
Lenze setting
50
rpm
9999 1500 rpm
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00012 | Accel. time - main setpoint
Data type: UNSIGNED_32
Index: 24563
d
= 5FF3
h
FB: Acceleration time of the ramp generator for the main speed setpoint
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
s
999.9 2.0 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000