6i/o terminals – Lenze 8400 motec User Manual

Page 190

Advertising
background image

6

I/O terminals

6.2

Analog terminals

190

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Using terminal A1U/A1I as current input
In the Lenze setting, voltage signals in the range of 0 ... +10 V are evaluated via the A1U/A1I analog

input terminal. If current signals are to be detected instead, select "1: 0...20 mA" or "2: 4...20 mA in

C00034/1

.

Open-circuit monitoring
With a configuration as 4 ... 20 mA current loop, the error response set in

C00598

takes place in the

event of a wire breakage (Lenze setting: "1: Fault").

Advertising