Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

47

3

Commissioning

3.6

Commissioning of the "Switch-off positioning" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Tip!
Also check the other information on the nameplate against the motor data set in the drive

controller. You can find further information in the chapter entitled "

Motor selection/Motor

data

".

( 82)

Recommendations for the following application cases:

• If the controller and motor differ greatly from each other in terms of performance:

Set the Imax limit (in motor mode) in

C00022

to double the rated motor current.

• If a higher starting torque is required:

In idle state of the motor, set the Vmin boost in

C00016

in such a way that the rated

motor current flows at a field frequency of f = 3 Hz (display in

C00058

).

• If a high torque must be provided at small speeds without feedback:

Select "Sensorless vector control (SLVC) as motor control mode in

C00006

.

Related topics:

Motor control (MCTRL)

( 80)

Selecting the control mode

( 90)

V/f characteristic control (VFCplus)

( 96)

Sensorless vector control (SLVC)

( 122)