C00242 | l_pctrl_1: operating mode, C00243 | l_pctrl_1: acceleration time influence, C00244 | l_pctrl_1: deceleration time influence – Lenze 8400 motec User Manual

Page 370: C00245 | l_pctrl_1: pid output value, C00242, C00233, C00243, C00244, C00245, 11 parameter reference

Advertising
background image

11

Parameter reference

11.2

Parameter list | C00242

370

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00242

C00243

C00244

C00245

Parameter | Name:

C00242 | L_PCTRL_1: Operating mode

Data type: UNSIGNED_8

Index: 24333

d

= 5F0D

h

The

L_PCTRL_1

FB: Selection of the operating mode

• Depending on the selection, the blue switches in the displayed signal flow are set accordingly in the Engineer on

the Application parameter tab in the OverviewSignal flowProcess controller dialog level.

Selection list

(Lenze setting printed in bold)

Info

0 Off

The input setpoint nNSet_a is output without any

changes at the output nOut_a.

1 nNSet + nNSet_PID

nNSet_a and nAct_a are used as PID input values. The

arriving nNSet_a is additively linked to the value output

by the PID element.

2 nSet_PID

nSet_a and nAct_a are used as PID input values. The

input nNSet_a is not considered.

3 nNSet_PID

nNSet_a and nAct_a are used as PID input values. The

input nSet_a is not considered.

4 nNSet + nSet_PID

From version 04.00.00

nSet_a and nAct_a are used as PID input values. The

arriving nNSet_a setpoint is additively linked to the value

output by the PID element.

5 nNSet || nSet_PID

From version 04.00.00

nSet_a and nAct_a are used as PID input values. The

setpoint nNSet_a is output at the output nOut_a . The

PID output value is output at the output nPIDOut_a.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00243 | L_PCTRL_1: Acceleration time influence

Data type: UNSIGNED_32

Index: 24332

d

= 5F0C

h

The

L_PCTRL_1

FB: Acceleration time for showing the PID output value

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 5.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00244 | L_PCTRL_1: Deceleration time influence

Data type: UNSIGNED_32

Index: 24331

d

= 5F0B

h

The

L_PCTRL_1

FB: Deceleration time for masking out the PID output value

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 5.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00245 | L_PCTRL_1: PID output value

Data type: INTEGER_16

Index: 24330

d

= 5F0A

h

The

L_PCTRL_1

FB: Display of the output value of the PID process controller

Display range

(min. value | unit | max. value)

-199.9

%

199.9

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100