Commissioning

3.8

Control via field package ("key-operated switch operation")

56

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Special cases

• Special case  - direction of rotation is preselected and manual control is switched on via key-

operated switch: The drive is stopped via quick stop. The blue LED is blinking to call the user's

attention to the operating error.

• The rotation direction switch has to be first brought into "stop" position before the drive will

be ramped up to setpoint speed.

• Special case  - direction of rotation of rotation is preselected and manual control is switched

off via key-operated switch: The drive is stopped via quick stop. The blue LED is blinking during

quick stop. When the drive has reached standstill, the quick stop function is stopped and the

drive is again lead to the speed specified by the application.

Up to and including version 04.xx.xx

, the QSP ramp in

C00105

must be set to maximally 5 s.

After 5 s, the quick stop function is aborted and the drive is again led to the speed specified

by the application.

From version 05.00.00 onwards

, longer QSP ramps are possible.

[3-5]

Example: Special cases regarding manual control

Setpoint speed and ramps from the application

v(t)

t

t

TRUE

FALSE

DI3

LocalSetValue (P1)

0

t

t

TRUE

FALSE

DI5

C00461/1

C00461/1

LED

C00105

0

1

QSP

QSP

LED

C00105

Œ

Œ

Firmware-Version < 05.00.00:

max. 5 s