2 led status display, Led status display, 9diagnostics & error management – Lenze 8400 motec User Manual

Page 284

Advertising
background image

9

Diagnostics & error management

9.2

LED status display

284

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.2

LED status display

Tip!

• Information on failures can be transmitted e.g. to a master control via the fieldbus.

From version 04.01.00 onwards

, the brightness of the green LED can be reduced via bit 0

and bit 1 in

C00143

if the green light is too bright or disturbing for your application.

Information on some operating states can be quickly ob-

tained via the two-colored LED display on the top of the

device.
The meaning can be seen from the table below.

green

"DRIVE READY"

red

"DRIVE ERROR"

Description

Device status

(Display in

C00137

)

OFF

OFF

OFF or initialisation active

Init

OFF

Safe torque off is active

SafeTorqueOff

OFF

Device is ready to start

ReadyToSwitchOn

OFF

Device is switched on

SwitchedOn

OFF

Motor data identification/operation

OperationEnabled

The controller is ready to switch on, switched

on or the operation is enabled and a warning

is indicated.

OFF

Fault active

Trouble

OFF

Fault active

Fault

Legend

Meaning of the symbols used to describe the LED states:

LED is flashing once approx. every 3 seconds (slow flash)

LED is flashing once approx. every 1.25 seconds (flash)

LED is flashing twice approx. every 1.25 seconds (double flash)

LED is blinking every second

LED is permanently on