Delayed disconnection in partial-load operation ("Sleep Mode")

504

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

13.2

Delayed disconnection in partial-load operation ("Sleep Mode")

Task:
If the drive remains below a minimum load threshold for a longer period of time, the drive is to be

switched off for saving energy. If the setpoint exceeds the minimum load threshold, the drive is to

start again.

Solution:
The GP function "Analog comparison" (

L_Compare_1

) serves to monitor the setpoint speed. As soon

as it falls below the set switch-off threshold, the switch-off delay starts. After the set delay time has

expired, the drive switches off itself.

• The switch-off delay is implemented with the GP function "Binary delay element"

(

L_DigitalDelay_1

).

• As soon as the setpoint exceeds the switch-off threshold again, the drive restarts.

[13-3] Basic signal flow

Example parameter setting:

Digital

Delay

Compare

|IN1| < |IN2|

IN2

NSet

C00472/1

30 %

IN1

LA_NCtrl: bRFG_0

C00720/1

C00720/2

On delay

Off delay

LS_DigitalOutput: bRelay

bJog1

bJog2

nNSet_a

0

0
3

2

1

2

0

1

2

C00039/1
C

/2

00039

C

/2

00039

3

SetSpeedValueEff

bJogSpeed1

bJogSpeed2

nMainSetValue_a

C00680

Function

Parameter

Info

Setting

Info

Settings for device control

C00141

Auto-start option

0x00

Starting performance of the controller:

No inhibit after mains connection.

Assignment of the input/output terminals

C00621/1

LS_DigitalOutput:bRelay

220:

L_DigitalDelay_1

_bOut

The relay is triggered by the binary delay

element.

GP function "Analog comparison"

L_Compare_1

C00680

L_Compare_1: Fct.

6: |In1| < |In2|

Comparison operation:

|AIn1_Out| < |

C00472/1

|

C00700/13

L_Compare_1: nIn1_a

13: SetSpeedValueEff Comparison value 1 is the input value of

the setpoint generator

L_NSet_1

select-

ed via the JOG inputs.

C00700/14

L_Compare_1: nIn2_a

20: nPar1_a

The comparison value 2 is selected via

the free parameter

C00472/1

.

C00472/1

LS_ParFree_a: Value 1

30.0 %

Selection of the comparison value 2

(switch-off threshold).

GP function "Binary delay element"

L_DigitalDelay_1

C00720/1

L_DigitalDelay_1: On delay

10 s

Switch-on delay (= switch-off delay for

the drive)

C00720/2

L_DigitalDelay_1: Off delay

1 s

Switch-off delay (= switch-on delay for

the drive)

C00701/23

L_DigitalDelay_1: bIn

215:

L_Compare_1_bOut

Input value of the delay element is the re-

sult of comparison.