3 interface description, 1 "ac drive profile" control word, Interface description – Lenze 8400 motec User Manual

Page 234: Ac drive profile" control word, D as, Ac drive profile" control, Word, 7technology applications

Advertising
background image

7

Technology applications

7.3

TA "Actuating drive speed (AC Drive Profile)"

234

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.3.3

Interface description

7.3.3.1

"AC Drive Profile" control word

• Display parameter:

C01351/1

• Will only be set and evaluated if the "AC Drive Profile" application is set in

C00005

.

• If required, you can set an inversion for individual control bits in

C00890/1

which is included

in this display.

• The bit assignment of the control word can be obtained from the following table:

All input and output interfaces are described in the subchapter entitled "

Interface

description

" of the "speed actuating drive" application.

( 206)

Bit

Name

Function

Bit 0 Run Forward

Connections between Run1 and Run2 and trigger events can be found in the

EtherNet/IP™ communication manual.

Bit 1 Run Backward
Bit 2 Fault Reset

01 ≡ Resetting an error

0 ≡ No response

Bit 3

Reserved

-

Bit 4

Reserved

-

Bit 5 Ctrl from Net

Run/Stop control

0 ≡ Run/Stop control via local setting in the device or terminal

1 ≡ Run/Stop control via network (e.g. from the scanner)

Bit 6 Ref from Net

Status of the reference speed / reference torque

0 ≡ Reference via local setting in the device or terminal

1 ≡ Reference via network (e.g. from the scanner)

Bit 7 ... 15