C00076 | ti current controller, C00079 | sc: settings, C00081 | rated motor power – Lenze 8400 motec User Manual

Page 346: C00084 | motor stator resistance, C00081, C00084, C00076, Rate, Moto, Depend o

Advertising
background image

11

Parameter reference

11.2

Parameter list | C00076

346

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00076

C00079

C00081

C00084

Parameter | Name:

C00076 | Ti current controller

Data type: UNSIGNED_16

Index: 24499

d

= 5FB3

h

From version 03.00.00

Reset time Ti of the current controller for certain inverter functions (parameter identification, flying restart circuit)

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

ms

500.00 10.61 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00079 | SC: Settings

Data type: UNSIGNED_8

Index: 24496

d

= 5FB0

h

From version 04.00.00

Configuration of different options for sensorless control for synchronous motors (

SLPSM

)

Selection list

0 Off
1 On

Subcodes

Lenze setting

Info

C00079/1

0: Off

Reserved

C00079/2

0: Off

Reserved

C00079/3

0: Off

Reserved

C00079/4

1: On

Field weakening for synchronous motors

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00081 | Rated motor power

Data type: UNSIGNED_16

Index: 24494

d

= 5FAE

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.

Note:

It is mandatory to give the rated motor power for the sensorless vector control (

SLVC

).

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

kW

99.00 11.00 kW

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00084 | Motor stator resistance

Data type: UNSIGNED_32

Index: 24491

d

= 5FAB

h

After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

0

mohm

200000 330 mohm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1