Technology applications

7.2

TA "Actuating drive speed"

212

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.2.2.2

wDeviceStateWord status word

The wDeviceStateWord status word provided by the device control contains all information relevant

for controlling the controller.

• In control mode "40: Network (MCI/CAN)" the status word is transmitted to the master control

as process data word via the port block

LP_Network_Out

.

• Display parameter:

C00150

• The bit assignment of the wDeviceStateWord status word can be obtained from the following

table.

Bit

Name

Function

Bit 0 SwitchOn

1 ≡ Change to the "

SwitchedOn

" device status

• This bit must be set in the control word to ensure that the device changes to

the "

SwitchedOn

" device state after mains connection without the need for a

master control specifying this bit via fieldbus.

Bit 1 DisableVoltage

1 ≡ Inhibit inverter control (IMP - pulse inhibit)

Bit 2 SetQuickStop

1 ≡ Activate quick stop (QSP).

Activate/deactivate quick stop ( 65)

Bit 3 EnableOperation

1 ≡ Enable controller (RFR)

• If control via terminals is performed, this bit must be set in the control word.

Otherwise the controller is inhibited.

Enable/Inhibit controller ( 65)

Bit 4 ModeSpecific_1

Reserved (currently not assigned)

Bit 5 ModeSpecific_2
Bit 6 ModeSpecific_3
Bit 7 ResetFault

1 ≡ Reset fault (trip reset)

• Acknowledge error message (if the error cause has been eliminated).

Reset error ( 66)

Bit 8 SetHalt

1 ≡ Activate stop function

• Stop drive via stopping ramp (in preparation).

Bit 9 reserved_1

Reserved (currently not assigned)

Bit 10 reserved_2
Bit 11 SetDCBrake

1 ≡ Activate DC-injection braking

Manual DC-injection braking (DCB) ( 151)

Bit 12 JogSpeed1

Activation of fixed speed 1 ... 3

Bit 13 JogSpeed2
Bit 14 SetFail

1 ≡ Set error (trip set)

Bit 15 SetSpeedCcw

0 ≡ Direction of rotation to the right (Cw)

1 ≡ Direction of rotation to the left (Ccw)

Bit

Name

Status

Bit 0 FreeStatusBit0

Free status bit 0 (configurable in

C00621/7

)

Not assigned in Lenze setting.

Bit 1 PowerDisabled

1 ≡ Inverter control inhibited (pulse inhibit is active)

Bit 2 FreeStatusBit2

Free status bit 2 (configurable in

C00621/8

)

In Lenze setting pre-assigned with LA_NCtrl_bImaxActive signal:

1 ≡ The current setpoint is internally limited (the controller operates at the

maximum current limit)

Bit 3 FreeStatusBit3

Free status bit 3 (configurable in

C00621/9

)

In the Lenze setting pre-assigned with LA_NCtrl_bSpeedSetReached signal:

1 ≡ Speed setpoint reached