Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

71

4

Device control (DCTRL)

4.2

Device state machine and device states

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.1

Init

In the "Init" device status

• is the controller directly after the supply voltage is switched on.
• the operating system is initialised.
• all device components (power section, communication unit, etc) are identified.
• the parameters are read out of the memory module.
• the settings of the DIP switches are read in and parameters are overwritten.
• it is checked whether the DC-bus voltage is within the tolerance zone and the precharge relay is

closed.

• the inverter is inhibited, i.e., there is no voltage output at the motor terminals.
• the communication via fieldbus or diagnostic interface does not work yet.
• the application is not yet processed.
• the monitoring mode is not yet active.
• the controller cannot be parameterised yet and no device commands can be carried out yet.

LED status display

Display in

C00137

Display in status word 1 (

C00150

)

Bit 11

Bit 10

Bit 9

Bit 8

Init

0

0

0

1

Note!

If the initialisation is completed, it changes automatically to the "

ReadyToSwitchOn

" de-

vice state.