C00090

C00091

C00092

C00093

C00094

Parameter | Name:

C00090 | Rated motor voltage

Data type: UNSIGNED_16

Index: 24485

d

= 5FA5

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.
Setting range

(min. value | unit | max. value)

Lenze setting

0

V

1000 400 V

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00091 | Motor cosine phi

Data type: UNSIGNED_8

Index: 24484

d

= 5FA4

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.
Setting range

(min. value | unit | max. value)

Lenze setting

0.40

1.00 0.85

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00092 | Motor magnetising inductance

Data type: UNSIGNED_16

Index: 24483

d

= 5FA3

h

After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

0.0

mH

6500.0 0.0 mH

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00093 | Power section identification

Data type: UNSIGNED_16

Index: 24482

d

= 5FA2

h

Display of the identification of the detected power section of the controller
Display range

(min. value | unit | max. value)

0

65535

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00094 | Password

Data type: INTEGER_32

Index: 24481

d

= 5FA1

h

No function in case of 8400 motec
Setting range

(min. value | unit | max. value)

Lenze setting

0

9999 0

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1