C00114 | dix inversion, C00115 | di1| di2: function, C00115/1 – Lenze 8400 motec User Manual

Page 351: C00114, Setting in, C00115, 11 parameter reference

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

351

11

Parameter reference

11.2

Parameter list | C00114

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00114

C00115

Parameter | Name:

C00114 | DIx inversion

Data type: UNSIGNED_16

Index: 24461

d

= 5F8D

h

The polarity of each digital input of the device can be inverted via this bit field.

Digital terminals

Setting range

(min. hex value | max. hex value)

Lenze setting

0x0000

0xFFFF 0x8000 (decimal: 32768)

Value is bit-coded: (= bit set)

Info

Bit 0  DI1 inverted

Inversion of digital input 1

Bit 1  DI2 inverted

Inversion of digital input 2

Bit 2  DI3 inverted

Inversion of digital input 3

Bit 3  DI4 inverted

Inversion of digital input 4

Bit 4  DI5 inverted

Inversion of digital input 5

Bit 5  DI6 inverted

Inversion of digital input 6

Bit 6  DI7 inverted

Inversion of digital input 7

Bit 7  DI8 inverted

Inversion of digital input 8

Bit 8  Reserved
Bit 9  Reserved

Bit 10  Reserved
Bit 11  Reserved
Bit 12  Reserved
Bit 13  Reserved
Bit 14  Reserved
Bit 15  RFR inverted

Inversion of digital input RFR (controller enable)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00115 | DI1| DI2: Function

Data type: UNSIGNED_8

Index: 24460

d

= 5F8C

h

From version 02.00.00

Function assignment of the digital terminals DI1 and DI2

Digital terminals

:

Function assignment

Selection list

Info

0 DI1=In1 | DI2=In2

DI1 = digital input

DI2 = digital input

1 DI1=FreqIn12 | DI2=In2

DI1 = 1-track frequency input

DI2 = digital input

2 (DI1/DI2)=FreqIn12 (2-track)

DI1 and DI2 = 2-track frequency input

3 (DI1/DI2=+-)=FreqIn12

DI1 = 1-track frequency input

DI2 = specification of direction

Subcodes

Lenze setting

Info

C00115/1

0: DI1=In1 | DI2=In2

Function assignment of DI1 and DI2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1