12 function library – Lenze 8400 motec User Manual

Page 440

Advertising
background image

12

Function library

12.1

L_MPot_1

440

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Outputs

Parameter

Identifier

Data type

Value/meaning

nOut_a

INT

Output signal

Parameter

Possible settings

Info

C00800

-199.9

%

199.9 Upper limit

• Lenze setting: 100.0 %

C00801

-199.9

%

199.9 Lower limit

• Lenze setting: -100.0 %

C00802

0.1

s

999.9 Acceleration time

• Lenze setting: 10.0 s

C00803

0.1

s

999.9 Deceleration time

• Lenze setting: 10.0 s

C00804

Inactive function

• Selection of response when

deactivating the motor

potentiometer via the input

bInAct.

0 Retain value

(Lenze setting)

No further action; nOut_a retains its

value.

1 Deceleration to 0

The motor potentiometer returns to

0 % within the deceleration time T

if

.

2 Deceleration to lower limit

The motor potentiometer runs to the

lower limit value (

C00801

) within the

deceleration time T

if

.

3 Without ramp to 0

Important for the emergency stop

function

The motor potentiometer output

immediately changes to 0 %

4 Without ramp to lower limit

The motor potentiometer output

immediately changes to the lower

limit value (

C00801

).

5 Acceleration to upper limit

The motor potentiometer runs to the

upper limit value (

C00800

) within

the acceleration time T

ir

.

C00805

Init function

• Selection of response when

switching on the device.

0 Load last value

(Lenze setting)

The output value being output

during mains power-off is saved non-

volatilely in the internal memory of

the controller. It will be reloaded

during mains power-on.

1 Load lower limit

The lower limit value (

C00801

) is

loaded during mains power-on.

2 Load 0

An output value = 0 % is loaded

during mains power-on.

Advertising