background image

4

Device control (DCTRL)

4.1

Device commands (C00002/x)

62

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.1.1

Load Lenze setting

The

C00002/1

= "1: On / start" device command resets the parameters to the Lenze setting which

are saved in the controller Firmware.

• Can only be executed if the controller is inhibited; otherwise, the feedback

C00002/1

= "6: No

access - controller inhibit" will be returned.

• All parameter changes made since the last saving of the parameter set will get lost!
• This device command has an effect on the settings of the parameters of the operating system,

application and module.

How to load the Lenze setting:

1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit con-

troller" device command (

C00002/16

= "0: Off / ready").

2. Execute the "Load Lenze setting" device command:

C00002/1

= "1: On / start"

The load process may take a couple of seconds. After the device command has been called

in

C00002/1

, a dynamic status information ("Work in progress"  "Off / Ready") is re-

turned.