6 operationenabled, Operationenabled, Changed to the – Lenze 8400 motec User Manual

Page 75: 4device control (dctrl)

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

75

4

Device control (DCTRL)

4.2

Device state machine and device states

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.6

OperationEnabled

In the "OperationEnabled" state

• is the controller if the controller inhibit is deactivated and no trouble ("Trouble") and fault

("Fault") are existent.

• the operation is enabled and the motor follows the setpoint defined by the active application

(with sensorless vector control only after magnetisation has been completed).

Depending on certain conditions, a status change takes place based on the "OperationEnabled" de-

vice status.

Related topics:

wDriveControl control word

( 211)

LED status display

Display in

C00137

Display in status word 1 (

C00150

)

Bit 11

Bit 10

Bit 9

Bit 8

OperationEnabled

0

1

0

1

Change condition

Changeover to the device status

Control bit "EnableOperation" in control word wDriveControl = "0"

OR terminal RFR = LOW level (controller inhibit).

SwitchedOn

Control bit "SwitchOn" = "0".

ReadyToSwitchOn

Undervoltage in the DC bus.

Trouble

/

Fault

(depending on

C00600/1

)

Error with error response "Trouble" occurs.

Trouble