1 prepare controller for commissioning, Prepare controller for commissioning, 3commissioning – Lenze 8400 motec User Manual

Page 35

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

35

3

Commissioning

3.5

Commissioning of the "Actuating drive speed" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.5.1

Prepare controller for commissioning

1. Wiring the power and control terminals

• Use the mounting instructions supplied with the controller in order to connect the power and

control terminals correctly.

• Assign the digital inputs so that your application can be displayed by one of the

preconfigured control modes (

C00007

) for terminal control:

2. Drive Unit: Check switches DIP1 and DIP2.

• DIP1/switch 1 must be set to "OFF" in order that no parameters of the memory module are

overwritten when the device is started.

• See display parameters

C01911

and

C01912

for details.

3. Communication Unit CANopen or PROFIBUS: Set DIP3 switch.

• See display parameters C00349 (CANopen) or C13920 (PROFIBUS) for details.

4. Position the drive unit carefully onto the communication unit and fix it using the four screws.
5. Inhibit controller: Set RFR terminal to LOW level or open the contact.
6. Switch on voltage supply of the controller.

• Information on some operating states can be quickly obtained via the two-colored LED

display on the top of the device.

LED status display

( 284)

7. Establish a connection to the controller, e.g. via USB diagnostic adapter:

• Remove the cover of the diagnostic interface on the top of the device and connect the USB

diagnostic adapter to the diagnostic interface.

• establish a connection between the USB diagnostic adapter and the PC via a free USB port.

Assignment of the digital terminals

Control mode

DI1

DI2

DI3

DI4

DI5

Terminals 0

JOG 1/3

JOG 2/3

DCB

Cw/Ccw

BrkRelease

Terminals 2

JOG 1/3

JOG 2/3

QSP

Cw/Ccw

BrkRelease

Terminals 11

Cw/Ccw

DCB

MPotUp

MPotDown

BrkRelease

Terminal 16

JOG 1/3

JOG 2/3

Cw/QSP

Ccw/QSP

BrkRelease

Abbreviations used:

JOG Selection of fixed setpoints 1 ... 3 parameterised in

C00039/1...3

DCB Manual DC-injection braking

Cw/Ccw CW/CCW rotation

QSP Quick stop

MPotUp Motor potentiometer: Increase speed

MPotDown Motor potentiometer: Reduce speed

Cw/QSP Fail-safe selection of the direction of rotation in connection with quick stop

Ccw/QSP

BrkRelease Release holding brake manually

• In the Lenze setting, the brake control is switched off (not active).

 Set operating mode in

C02580

.