Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

89

5

Motor control (MCTRL)

5.2

Motor selection/Motor data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to carry out automatic motor parameter identification:

1. Inhibit the controller if it is enabled, e.g. via the

C00002/16

device command or a LOW

signal at the RFR terminal.

2. Wait until the drive is at standstill.
3. Transfer the nameplate data to the following codes:

C00081

: Rated motor power

C00087

: Rated motor speed

C00088

: Rated motor current (according to the connection method /)

C00089

: Rated motor frequency (according to the connection method /)

C00090

: Rated motor voltage (according to the connection method /)

C00091

: Motor cos ϕ

4. Start motor parameter identification via the

C00002/23

device command.

5. Enable the controller again.

• Motor parameter identification starts.
• The motor parameter identification takes approx. 30 s.
• The identification is completed if the "0: Off / ready" message is displayed in

C00002/23

.

6. Inhibit controller again.

Note!

Motor parameter identification may be aborted by the controller if a special motor (e.g.

mid-frequency motor) is used or if there is a large deviation between inverter and motor

power.
Another cause for the abort of the motor parameter identification could be the

implausibility of the entered nameplate data, e.g. the entry P = 0 kW for the motor

power.