Device control (DCTRL)

4.2

Device state machine and device states

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.8

Fault

In the "Fault" device state

• is the controller if monitoring has caused a "Fault" error response.
• the motor has no torque (is coasting) due to the inhibit of the inverter.

The error must explicitly be reset ("acknowledged") in order to exit the device state, e.g. by the de-

vice command "

Reset error

" or via the control bit "ResetFault" in the control word wDriveControl.

Related topics:

wDriveControl control word

( 211)

Basics on error handling in the controller

( 283)

Error messages of the operating system

( 297)

LED status display

Display in

C00137

Display in status word 1 (

C00150

)

Bit 11

Bit 10

Bit 9

Bit 8

Fault

1

0

0

0

Note!

If an undervoltage in the DC bus of the drive controller occurs (error message "LU"), the

device changes to the "

Trouble

" status.

An additional error of higher priority leads the device into the "

Fault

" status.

According to the

Device state machine

, the device changes to the "

ReadyToSwitchOn

"

status after acknowledging the error although the undervoltage is still available!
If the "Inhibit at fault" auto-start option has been activated in

C00142

, explicit deactiva-

tion of the controller inhibit is required before the status can be abandoned.