C00604 | resp. to device overload (ixt), C00606 | resp. to motor overload (i·xt), C00607 | resp. to max. speed reached – Lenze 8400 motec User Manual

Page 387: C00620 | 16-bit system connection, C00604, C00606, C00620, C620/5, C620/6, C620/7

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

387

11

Parameter reference

11.2

Parameter list | C00604

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00604

C00606

C00607

C00620

Parameter | Name:

C00604 | Resp. to device overload (Ixt)

Data type: UNSIGNED_8

Index: 23971

d

= 5DA3

h

Response if the adjustable device utilisation threshold (

C00123

) is reached.

• The current device utilisation is displayed in

C00064

.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
4 WarningLocked

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00606 | Resp. to motor overload (I²xt)

Data type: UNSIGNED_8

Index: 23969

d

= 5DA1

h

Response when the motor load displayed in

C00066

reaches the value "100.00 %".

Motor overload monitoring (I2xt)

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
4 WarningLocked

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00607 | Resp. to max. speed reached

Data type: UNSIGNED_8

Index: 23968

d

= 5DA0

h

From version 02.00.00

Response when the maximum input frequency has been reached via the digital inputs.
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
4 WarningLocked

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00620 | 16-bit system connection

Data type: UNSIGNED_16

Index: 23955

d

= 5D93

h

Connection parameters: 16-bit inputs

• Selection of the 16 bit output signals to be connected to the 16 bit input signals

• The selection list contains all 16 bit output signals which can be assigned to the 16 bit inputs displayed by the

subcodes.

Selection list
See

selection list - analog signals

Subcodes

Lenze setting

Info

C00620/1

0: Not connected

Reserved

C00620/2

0: Not connected

Reserved

C00620/3

0: Not connected

Reserved

C00620/4

0: Not connected

Reserved

Advertising