4.1.3

Save parameter settings

If parameter settings are changed in the controller, those changes will be lost after mains switching

of the controller unless the settings have been saved explicitly.

Manual saving of parameter settings
The

C00002/7

= "1: On / start" device command saves the current parameter settings safe against

mains failure to the memory module of the controller.

Automatic saving of parameter changes

When you select "1: active" in

C00141/1

, automatic saving is activated and every parameter change

is saved automatically in the memory module. Thus, manual saving of parameter sets is not re-

quired anymore.

4.1.4

Importing EPM data

The

C00002/12

= "1: On / start" device command activates the automatic import of parameters

from the memory module after the error message "PS04: Par.set incompatible".

• The

C00002/12

= "0: Off / ready" device command deactivates this function again.

Note!

How to prevent a data loss:

• Do not switch off the supply voltage during the saving process.
• Only unplug the memory module if the device is switched off.

Stop!

Activating this function is not permissible if parameters are changed very frequently

(e.g. in case of cyclic writing of parameters via a bus system).
The maximum service life of the memory module amounts to one million writing cycles.

Make sure that this value will not be reached.