C00203 | product type code, C00204 | serial number, C00222 | l_pctrl_1: vp – Lenze 8400 motec User Manual

Page 366: C00223 | l_pctrl_1: tn, C00222, In percent, C00223, C00203/3, 11 parameter reference

Advertising
background image

11

Parameter reference

11.2

Parameter list | C00203

366

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00203

C00204

C00222

C00223

Parameter | Name:

C00203 | Product type code

Data type: VISIBLE_STRING

Index: 24372

d

= 5F34

h

Display of the types of the individual device components
Subcodes

Info

C00203/1

Type: Control card

C00203/2

Type: Power section

C00203/3

Type: Comm. module

C00203/4

Reserved

C00203/5

Type: Memory module

C00203/6

Type: Safety module

C00203/7

Reserved

C00203/8

Type: Complete device

C00203/9

Reserved

Read access  Write access  CINH  PLC-STOP  No transfer  COM  MOT

Character length: 24

Parameter | Name:

C00204 | Serial number

Data type: VISIBLE_STRING

Index: 24371

d

= 5F33

h

Display of the serial numbers of the individual device components
Subcodes

Info

C00204/1

Serial no.: Control card

C00204/2

Serial no.: Power section

C00204/3

Serial no.: MCI module

C00204/4

Reserved

C00204/5

Reserved

C00204/6

Reserved

C00204/7

Serial no.: Standard device

Read access  Write access  CINH  PLC-STOP  No transfer  COM  MOT

Character length: 24

Parameter | Name:

C00222 | L_PCTRL_1: Vp

Data type: INTEGER_16

Index: 24353

d

= 5F21

h

The

L_PCTRL_1

FB: Gain factor Vp for the PID process controller

Setting range

(min. value | unit | max. value)

Lenze setting

0.1

500.0 1.0

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00223 | L_PCTRL_1: Tn

Data type: UNSIGNED_16

Index: 24352

d

= 5F20

h

The

L_PCTRL_1

FB: Reset time Tn for the PID process controller

Setting range

(min. value | unit | max. value)

Lenze setting

20

ms

6000 400 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1