Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

49

3

Commissioning

3.6

Commissioning of the "Switch-off positioning" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3. Adapt the application parameters:

Tip!

• Click the Signal flow button to go down one dialog level to the signal flow of the

application with further possible parameter settings. See chapter "

Basic signal flow

".

( 242)

• The preconfigured I/O connection in the selected control mode can be changed via

configuration parameters. See chapter "

User-defined terminal assignment

".

( 191)

• Low-jerk traversing profiles can be implemented by means of S-shaped ramps.
• In the case of high breakaway torques combined with horizontal motion sequences,

"Sensorless vector control (SLVC)" can be used as motor control (

C00006

).

More detailed informaton on the technology application:

TA "Switch-off positioning"

( 238)

wDriveControl control word

( 244)

Terminal assignment of the control modes

( 246)

Setting parameters (short overview)

( 253)

Pre-assignment of the application

( 254)

Parameter

Lenze setting

Info

Value Unit

Accel. time - main setpoint

(

C00012

)

2.0 s

The setpoint is led via a ramp function generator with

linear characteristic. The ramp function generator

converts setpoint step-changes at the input into a ramp.

Note: These settings only apply if no other ramp times

have been selected at the FB

L_NSet_1

!

Decel. time - main setpoint

(

C00013

)

2.0 s

Reference speed

(

C00011

)

1500 rpm

All speed setpoint selections are provided in % and

always refer to the reference speed set in

C00011

.

The motor reference speed is indicated on the motor

nameplate.

Decel. time - quick stop

(

C00105

)

5.0 s

If quick stop is requested, motor control is decoupled

from the setpoint selection and, within the deceleration

time parameterised in

C00105

, the motor is brought to

a standstill (n

act

= 0).

Activate/deactivate quick stop ( 65)

Fixed setpoint 1

(

C00039/1

)

40.0 %

Fixed setpoints are selected in [%] based on the

reference speed (

C00011

).

Fixed setpoint 2 must be smaller than fixed setpoint 3!

Otherwise, the drive will be started with a low speed

and accelerated after the pre-switch off.

Fixed setpoint 2

(

C00039/2

)

60.0 %

Fixed setpoint 3

(

C00039/3

)

80.0 %