C00071 | ti speed controller, C00073 | vp imax controller, C00074 | ti imax controller – Lenze 8400 motec User Manual

Page 345: C00075 | vp current controller, C00075, C00071/3, C00073, C00074, Reset time ti, 11 parameter reference

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

345

11

Parameter reference

11.2

Parameter list | C00071

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00071

C00073

C00074

C00075

Parameter | Name:

C00071 | Ti speed controller

Data type: UNSIGNED_16

Index: 24504

d

= 5FB8

h

From version 03.00.00

Reset time Ti of the speed controller for sensorless control for synchronous motors (

SLPSM

)

Setting range

(min. value | unit | max. value)

0.0

ms

6000.0

Subcodes

Lenze setting

Info

C00071/1

0.0 ms

Reserved

C00071/2

0.0 ms

Reserved

C00071/3

100.0 ms

SLPSM

: Ti speed controller

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00073 | Vp Imax controller

Data type: UNSIGNED_16

Index: 24502

d

= 5FB6

h

Amplification factor Vp for Imax controller
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

16.00 0.25

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00074 | Ti Imax controller

Data type: UNSIGNED_16

Index: 24501

d

= 5FB5

h

Reset time Ti for Imax controller
Setting range

(min. value | unit | max. value)

Lenze setting

12

ms

9990 65 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00075 | Vp current controller

Data type: UNSIGNED_16

Index: 24500

d

= 5FB4

h

From version 03.00.00

Gain factor Vp of the current controller for certain inverter functions (parameter identification, flying restart circuit)

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

V/A

500.00 7.00 V/A

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100