CE2: CAN RPDO2 [xx.0135.00002]

CI01: Module missing/incompatible [xx.0140.00013]

PS01: No memory module [xx.0144.00001]

PS02: Par. set invalid [xx.0144.00002]

PS03: Par. set device invalid [xx.0144.00003]

Response (Lenze setting printed in bold)

Setting:

C00593/2

( Adjustable response)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

CAN interface: Time monitoring for RPDO2 has tripped.

• RPDO2 has not been received within the monitoring

time set in C00357/2 or was faulty.

• Set correct telegram length for CAN master (transmit-

ter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time C00357/2 or switch off time

monitoring.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

There is a connection problem between the communica-

tion unit and the drive unit or an incompatibility.

• Check installation of the 8400 motec.

• In case of an incompatibility, either the communica-

tion unit or the software of the drive unit is out of

date. In this case, please contact Lenze.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Memory module is either not available or not snapped

into place correctly.

• If a memory module has been provided: Plug the

memory module into the slot of the drive unit intend-

ed for this purpose.

• If a memory module has been provided: Check if the

memory module has been plugged-in correctly.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The parameter set stored in the memory module is

invalid. The reason for this can be as follows:

• Incomplete storage of the parameter set due to volt-

age failure.

• The plugged-in memory module stems from a device

with more recent firmware (compare

C00099

) or from

a different device type (e.g. 8400 BaseLine).

The error can only be eliminated by loading the Lenze

setting with the device command

C00002/1

= "1: On /

start".

• In order to prevent the error, do not switch off the

voltage during the saving process.

• If the parameter set is to be transferred from one de-

vice with a higher version to a device with a lower ver-

sion, use the "copy parameter set" function of the

keypad. Make sure that you do not use functions that

are not available in the older device.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The parameter set in the device is invalid.

Consultation with Lenze required.