3

Commissioning

3.8

Control via field package ("key-operated switch operation")

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to reset the field package functionality using the »Engineer«

(e.g. after the Lenze setting has been loaded):

1. Show service codes in the »Engineer«:

• Execute the ExtrasOptions command to open the Options dialog box.
• Go to the Service tab and activate the Show invisible parameters option.

2. Go to the All parameters tab and set the

C00460

service code to "1: On" to activate the field

package functionality.
The links of the digital inputs DI3, DI4 and DI5 via the configuration parameters

C00621

and

C00701

are evaluated independently of the field package functionality. Hence, make

sure to not assign more functions to these three digital inputs if the switchbox

functionality is used.

Note!

When loading the Lenze setting into the controller, reset the field package functionality

afterwards using the »Engineer« (see the following instructions).