Df10: time out i/o micro [xx.0145.00010, Df11: oscillator fail [xx.0145.00011, Df12: math error [xx.0145.00012 – Lenze 8400 motec User Manual

Page 315: Df13: dma error [xx.0145.00013, Ioc: comm module changed [xx.0145.00198, Xx.0145.00010, Xx.0145.00011, Xx.0145.00012, Xx.0145.00013, Xx.0145.00198

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

315

9

Diagnostics & error management

9.8

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

dF10: time out I/O micro [xx.0145.00010]

dF11: oscillator fail [xx.0145.00011]

dF12: math error [xx.0145.00012]

dF13: DMA error [xx.0145.00013]

IoC: Comm module changed [xx.0145.00198]

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Device error

• Make sure that the Drive Unit and the Communica-

tion Unit are connected correctly to each other. Check

the pins of the COM plug and firmly tighten all screws

of the 8400 motec cover.

• Mains switching or restart of the controller, respec-

tively.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Device error

• Mains switching or restart of the controller, respec-

tively.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Device error

• Mains switching or restart of the controller, respec-

tively.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Device error

• Mains switching or restart of the controller, respec-

tively.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Since the last power-down, the Communication Unit has

been replaced. The fieldbus, the safety circuit or the

module type has changed. It cannot be assumed any-

more that the available parameter setting matches the

new Communication Unit.

Switch off the device and mount the previous Communi-

cation Unit again. Then acknowledge the error with the

C00002/19

= "1: On / start" device command. All com-

munication parameters in the device will be set to the

Lenze setting of the currently used Communication Unit.

Changed communication parameters must be reset and

saved.