3.5 MP920 Module Definitions

3-27

3

1. Dual Module Setting

When setting a Dual Module, the same type of Module must be defined in another slot
and the Dual Module setting for the Modules must be set to "Enable."

2. Dual Setting Error

An error will occur when the settings are saved if Dual Modules are set but there are not
two Dual Modules, i.e., if there is just one Module or more than two Modules.

3. Dual Transmission Paths

With 215IF Modules, it is possible to specify a dual transmission path. The Dual Mod-
ule setting must also be made for the dual transmission path.

Cir (Dual) (Dual Transmission Paths)

Sets a dual 215IF transmission path.

Replacement (Hot Swapping)

Hot swapping (removal/insertion under power) is not supported in the current version.

I/O Start Register

Inputs the leading register number for each Module's I/O.

• Register Ranges

The following table shows the fixed range of registers for each Module.

Table 3.1 Register Ranges

Module

Minimum Number of Words

Maximum Number of Words

MP920

-

-

LIO-01

-

-

215IF

0 Hex

800 Hex

217IF

-

-

218IF

-

-

260IF

-

-

LIO-01

1 Hex

10 Hex

AI-01

1 Hex

8 Hex

AO-01

1 Hex

4 Hex

DI-01

1 Hex

4 Hex

DO-01

1 Hex

4 Hex

CNTR-01

1 Hex

40 Hex

SVA-01

400 Hex

400 Hex

SVA-02

400 Hex

400 Hex

PO-01

400 Hex

400 Hex

SVB-01

400 Hex

400 Hex