Mlink definition settings, Transmission parameters tab page – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual

Page 249

Advertising
background image

Module Configuration Definitions

3.7.10 MLINK (CERF) Definitions

3-154

3

„

MLINK Definition Settings

This section describes the settings on the tab pages.

Transmission Parameters Tab Page

This tab page is used to set the parameters required to use the MLINK transmission system.

Table 3.24 Message Trust Levels

Table 3.25 Maximum Number of Slave Stations

Setting Item

Details

Default

Master/Slave

Sets whether to use the Machine Controller as a
master station or as a slave station.

Master

Own Station
Address

When the Machine Controller is being used as a
master station, the local station address is fixed at
0 and cannot be changed. When it is being used as
a slave station, set a station address between 1
and 14.

0

Message Trust
Level

Sets the error control method used when sending
MEMOBUS commands. Set the level from the
table of message trust levels given below.

0

Max Slave ST
Number
(Maximum Slave
ST Number)

One of three levels can be selected. Refer to the
table of the maximum number of slave stations
given below. Set the number according to the
scale of the system.

14 stations

Scan

Set to High or Low.

Low

Level

Details

0

Send command just once and wait indefinitely for a response from the destina-
tion.

1

Send command just once and resend if a response is not received within 8 sec-
onds.

2

When sending the command, send each word of data twice consecutively and
wait indefinitely for a response from the destination. This method improves
transmission quality but reduces transmission efficiency by 50%.

Number of Slave

Stations

Baud Rate

Communications

Cycle

14 stations

4 Mbps

2 ms