Deleting assignment data – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual

Page 154

Advertising
background image

3.5 MP920 Module Definitions

3-59

3

Table 3.8 Pairing Conditions

Deleting Assignment Data

The procedure to delete the assignment data for one connection is given below.

1. Move the cursor to the connection to be deleted.

2. Click Edit (E) and then Assignment Delete (C) from the 218IF Transmission Defini-

tions menu.

3. The assignment data selected in step 1. will be deleted.

Protocol Type and
Code Settings

The following table shows the possible combinations of the Protocol
Type and Code (data format) settings for each connection.
The Protocol Type and Code Combinations are shown below.

Protocol Type

Code

Extended MEMOBUS

Binary or ASCII

MEMOBUS

RTU or ASCII

MELSEC

Binary or ASCII

General-purpose

Binary or ASCII

Parameter

CNO

XX

YY

Pairing Condition

Local Station's
Port Number

10000

20000

Set each other's port
numbers.

Remote Station's
Port Number

20000

10000

Remote Station's
IP Address

134.237.127.004

134.237.127.004

Set both to the local
station's IP address.

Connection Type

TCP

TCP

Set both to the same
value.

Protocol Type

Extended
MEMOBUS

Extended
MEMOBUS

Code

Binary

Binary

Remote Station's
Ethernet Address

12:34:56:78:9A:BC

12:34:56:78:9A:BC

Consistency Item

Details