Input format for constants, Inputting instructions – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual

Page 393

Advertising
background image

Ladder Logic Programming

7.3.5 Entering Ladder Instructions

7-26

7

„

Input Format for Constants

The following table shows the input format for constants.

„

Inputting Instructions

Inputting instructions can be divided into several patterns. These will be described using the
following instructions.

• Math, logic, and comparison instructions
• Conditional instructions
• Functions
• MOVW, XCHG, etc.
• SEE
• END
• Inline comments

Input Value

Window

Display

Input

String

Explanation

Decimal

Integer

00100

100

Use numerals between 0 and 9.
Place a minus sign (-) in front of
negative values.

Double-
length
Integer

0000010000

10000L

Use numerals between 0 and 9 and
enter L at the end of the value.
Place a minus sign (-) in front of
negative values.
If the input value is greater than
32,767 or less than -32,768, the
value will become a double-length
integer automatically, even with-
out an L at the end of the value.

Real
Number

100.1E

100.1E

Use numerals between 0 and 9 and
place an E at the end of the value.
Place a minus sign (-) in front of
negative values.
If the input value includes a dot (.),
the value will become a real num-
ber automatically, even without an
E at the end of the value.

Hexadecimal

Integer

H32FF

H32FF

Place an H at the beginning of the
value, and use 0 to 9 and A to F.

Double-
length
Integer

H000032FF

H32FFL

Place an H at the beginning of the
value, and use 0 to 9 and A to F.
Place an L at the end of the value.
If the input value is longer than 4
digits, the value will become a dou-
ble-length integer automatically,
even without L at the end of the
value.