The analog input definitions window original menus – Yaskawa MP900 Series Machine Controller for Standard Operation User Manual

Page 177

Advertising
background image

Module Configuration Definitions

3.5.15 Analog Input Definitions

3-82

3

Fig 3.16 Analog Input Definitions Window

„

The Analog Input Definitions Window Original Menus

„

Setting Analog Input Definitions

Setting Allocation Data

The Analog Input Definitions determine the operation and the disable status of the analog

inputs.

Menu Command

Function

Edit (E)

Assignment Delete (D)

Deletes allocation data.

Set (S)

Offset/Gain (O)

Sets the offset and gain.

Setting Item

Details

Channel

Displays the channel number (1 to 8).

In Range
(Input Range)

Selects the input range: -10 to +10 V, 0 to 10 V, or 0 to 20 mA.

D

Controls the register's disable setting.

• :

Enabled

• :

Disabled

REG-No.

Input the number of the register (I register number) that handles the
input.

Word (Number of
Words)

Displays the number of consecutive register words.

SCAN

Sets the transmission processing scan in which inputs are serviced.

• HIGH: High-speed scan
• LOW:

Low-speed scan

Current Data

In online mode, these columns display the current value in the order
of current value, units, and hexadecimal current value of the
Machine Controller's register. The unit corresponds to the unit set in
In Range. In offline mode, nothing will be displayed.