Yaskawa MP900 Series Machine Controller for Standard Operation User Manual

Page 479

Advertising
background image

A-3

A

Table A.3 CPDH_CPU_nnn

AEND instruction structure incorrect
(CPDH_CMP_007)

The AEND instruction structure is
incorrect.

Match the number of ABOX or SBOX
instructions and AEND instructions in the
SFC Action Box Window.

Too many SFC flowchart steps
(CPDH_CMP_008)

The maximum number of steps in
the SFC flowchart has been
exceeded.

Reduce the number of SFC flowchart steps.

Too many SFC output bits
(CPDH_CMP_009)

The maximum number of SFC
output bits has been exceeded.

Reduce the number of SFC output bits to
within the permissible range.

ABOX instruction structure incorrect
(CPDH_CMP_010)

The ABOX instruction structure is
incorrect.

Correct the ABOX instruction and the rela-
tionship between ABOX and SBOX instruc-
tions.

SFC flowchart branches exceeded
(CPDH_CMP_012)

The number of SFC flowchart
branches has been exceeded.

Reduce the number of SFC flowchart
branches.

SFC flowchart structure incorrect
(CPDH_CMP_013)

The SFC flowchart structure is
incorrect.

Check the SFC flowchart for incorrect start,
end, or branch settings.

Too many SFC flowchart step boxes
(CPDH_CMP_014)

The number of SFC flowchart
step boxes has been exceeded.

Reduce the number of SFC flowchart step
boxes.

Expansion program (table or other
program) structure incorrect
(CPDH_CMP_015)

The table or other type expansion
program structure is incorrect.

Check the expansion program for incorrect
expansion program conversions in the CP-
717. Contact your Yaskawa representative if
the error persists.

Error Message

Probable Cause

Possible Correction

Error Message

Probable Cause

Possible Correction

1 DWG/FN object too large
(CPDH_CPU_021)

The size of one drawing or func-
tion object is too large.

Reduce the size of the drawing or function
objects.

Source memory control error
(CPDH_CPU_040)

A source memory control error
has occurred.

Execute the load again.

1 DWG/FN object too large
(CPDH_CPU_0B1)

The size of one drawing or func-
tion object file is too large.

Reduce the size of the drawing or function
objects.
Reduce the number of steps.
Reduce the number of # registers.

Machine Controller cannot run due to
program memory error or watchdog time
out
(CPDH_CPU_041)

The Machine Controller cannot
run due to a program memory
error or a watchdog time out.

Execute loading.

Cannot use this function because
Machine Controller is online
(CPDH_CPU_04D)

Load operation cannot be per-
formed because the Machine Con-
troller is online.

Stop Machine Controller operation using the
System Configuration Window.

Transmission error
(CPDH_CPU_090)

A transmission error has occurred.

• Repeat the operation.
• Check if the connectors are set properly.
• Check that there is no noise interference.

Incorrect processing request from CP-717
(CPDH_CPU_091)

There is an error in the processing
request from the CP-717.

Repeat the operation.
Replace the Machine Controller or CP-717 if
the error persists.

Incorrect processing request from CP-717
(CPDH_CPU_092)

There is an error in the processing
request from the CP-717.

Repeat the operation.
Replace the Machine Controller or CP-717 if
the error persists.