3.5 MP920 Module Definitions

3-81

3

„

Saving, Deleting, and Closing Counter I/O Definitions

Refer to the procedures in 3.3 Basic Individual Module Definition Operations for details.

3.5.15 Analog Input Definitions

This section explains how to set the Analog Input Definitions.

„

Outline of the Analog Input Definitions

The AI-01 Module is equipped with 8 analog input (AI) channels. The overall input circuit is
isolated, but the channels are not isolated from each other.

It is possible to use 1, 2, 4, or 8 channels. Processing speed can be improved by selecting
fewer channels because it is not necessary for the CPU to scan all 8 channels.

Input servicing is performed at fixed intervals, once for each scan (high-speed or low-speed)
in the CPU-01 Module. Each channel can be set to the high-speed or low-speed scan inde-
pendently.

Set the scan timing and allocates registers to 4 analog input channels in the Analog Input
Definitions Window.

Three types of analog input ranges must be selected.

„

Opening the Analog Input Definitions Window

Open the Analog Input Definitions Window according to the procedure in 3.3 Basic Individ-
ual Module Definition Operations
.

CN1

Input

Port

S

ystem Bus Connector

S

ystem Bus

Interface

Isolation

Circuit

A/D

Convertor

Ana

log

m

u

lti

ple

xer