5 Motion Commands

5.2.3 Zero Point Return (ZRET)

5-50

* 1. The SERVOPACK P-OT signal.
* 2. The SERVOPACK N-OT signal.

Note)The stopping method when the OT signal is detected depends on the setting of

SERVOPACK parameters.

Note) Reverse type in

: Parameters only for the SVA-01 Module.

INPUT signal (OB

05B)

Start

Zero Point

Creep Speed

(OL

40)

Home Offset

(OL

42)

Positioning Speed

(OL

10)

INPUT signal (OB

05B)

Start

Zero Point

Creep Speed

(OL

40)

Home Offset

(OL

42)

Positioning Speed

(OL

10)

Creep Speed

(OL

40)

NOT

*2

POT

*1

NOT

*2

POT

*1

Parameter

Name

Setting

OW††3C

Home Return Type

19: INPUT Only Method

OL††10

Speed Reference

Set the positioning speed to use after detecting the INPUT signal. The
sign is ignored. The travel direction will depend on the sign of the Home
Offset.

OL††18

Speed Override

This parameter allows the Zero Point Return speed to be changed
without changing the Speed Reference (OL††10). Set the
override value as a percentage of the Speed Reference. This
setting can be changed during operation.
Setting range: 0 to 32767 (0% to 327.67%);
Setting unit: 1 = 0.01%

OL††40

Creep Speed

Set the speed to use when starting a zero point return. The travel direction
will depend on the sign of the creep speed.

OL††42

Home Offset

Set the distance to travel from the point the INPUT signal is detected. The
travel direction will depend on the sign.

OB††05B

INPUT Signal for Zero
Point Return

This signal must be turned ON from the ladder program.