[ c ] Monitoring Parameters

No.

Name

Unit

Default Value

Range

IW††00

Drive Status

Bit setting

IW††01

Over Range Parameter Number

0 to 65535

IL††02

Warning

Bit setting

IL††04

Alarm

Bit setting

IW††08

Servo Command Type Response

0 to 65535

IW††09

Servo Module Command Status

Bit setting

IW††0A

Motion Subcommand Response Code

0 to 65535

IW††0B

Motion Subcommand Status

Bit setting

IW††0C

Position Management Status

Bit setting

IL††0E

Machine Coordinate Target Position (TPOS)

Reference unit

−2

31

to 2

31

−1

IL††10

Target Position (CPOS)

Reference unit

−2

31

to 2

31

−1

IL††12

Machine Coordinate System Position (MPOS)

Reference unit

−2

31

to 2

31

−1

IL††16

Machine Coordinate Feedback Position (APOS)

Reference unit

−2

31

to 2

31

−1

IL††18

Machine Coordinate Latch Position (LPOS)

Reference unit

−2

31

to 2

31

−1

IL††1A

Position Error (PERR)

Reference unit

−2

31

to 2

31

−1

IL††1C

Target Position Difference Monitor

Reference unit

−2

31

to 2

31

−1

IL††1E

POSMAX Number of Turns

Reference unit

−2

31

to 2

31

−1

IL††20

Speed Reference Output Monitor

pulse/s

−2

31

to 2

31

−1

IW††2C

Network Servo Status

Bit setting

IW††2D

Servo Alarm Code

−32768 to 32767

IW††2E

Network Servo I/O Monitor

Bit setting

IW††2F

Network Servo User Monitor Information

Bit setting

IL††30

Servo User Monitor 2

−2

31

to 2

31

−1

IL††34

Servo User Monitor 4

−2

31

to 2

31

−1

IW††36

Servo Constant Number

0 to 65535

IW††37

Auxiliary Servo User Constant Number

0 to 65535

IL††38

Servo User Constant

−2

31

to 2

31

−1

IL††3A

Auxiliary Servo User Constant

−2

31

to 2

31

−1

IW††3F

Motor Type

0, 1

IL††40

Feedback Speed

Depends on speed unit.

−2

31

to 2

31

−1

IL††42

Torque (Thrust) Reference Monitor

Depends on torque unit.

−2

31

to 2

31

−1

IL††56

Fixed Parameter Monitor

−2

31

to 2

31

−1

IL††5E

Absolute Position at Power OFF (Low Value)

pulse

−2

31

to 2

31

−1

IL††60

Absolute Position at Power OFF (High Value)

pulse

−2

31

to 2

31

−1

IL††62

Modularized Position at Power OFF (Low Value)

pulse

−2

31

to 2

31

−1

IL††64

Modularized Position at Power OFF (High Value)

pulse

−2

31

to 2

31

−1

Advertising