9.1 Controlling Vertical Axes

9-3

9.1.2 Connections to

Σ-II and Σ-III SERVOPACK

( 1 ) Connection Example

A circuit is configured to turn the brake ON and OFF using the /BK contact output signal from the
SERVOPACK and a brake power supply. The standard connections are shown in the following
diagram.

* 1. The output terminal is allocated using parameter Pn50F.2.
* 2. Brake control relay contact
* 3. There are 200-V and 100-V brake power supplies.

( 2 ) Parameter Settings

[ a ] PN50F.2 (Output Signal Selection 2)

The following parameter determines which pin of CN1 will be used to output the /BK signal.

* Select which terminal is used to output /BK. (Set to 2 in this example.)

M

BK

PG

U
V

W

CN2

AC

DC

BK-RY

+24 V

L1
L2
L3
L1C
L2C
27-

28-

/BK+

/BK-

A (1)

B (2)

C (3)

D (4)

E (5)

F (6)

BK-RY

∗1

∗1

∗2

Red

Black

Blue or

yellow

White

Brake power supply

*3

Power supply

SGDH or SGDS

SERVOPACK

Servomotor
with a brake

Parameter

Name

Unit

Setting

Range

Default

Control Mode

Pn50F.2

Output Signal Selection 2

0 to 3

0

Speed, torque, position
control

Parameter

Setting

Output Terminal (CN1)

Pn50F.2

0

1

25

26

2

27

28

3

29

30

Pn50F.2

1
2
3

CN1-25, 26(SO1)
CN1-27, 28(SO2)
CN1-29, 30(SO3)

Output Terminals

/BK brake
interlock output