10.2 Error Detection

10-27

Er

ror

s (cont

’d)

Blinking

Blinking

Hardware Error

(Number of LED blinks indicates
error type.)
1:

2: ROM diagnostic error
3: RAM diagnostic error
4: CPU diagnostic error
5: FPU diagnostic error
6: Shared memory diagnostic error
7: JL-080 diagnostic error

Hardware failure in the Module
The Module must be replaced.

Lit

Blinking

Software Error

(Number of LED blinks indicates
error type.)
1:

2: Watchdog timer over error
3: Address error (read) exception
4: Address error (write) exception
5: FPU exception error
6: Illegal general command
7: Illegal slot command
8: General FPU inhibited error
9: Slot FPU inhibited error
10: Watchdog timer over error

If a watchdog timer over error occurs, it is possible that the user
program's processing time is longer than the scan time setting.
Check the user program and the scan time setting.

W

rit

in

g F

la

sh

Memory

Not lit

Lit

Erasing Flash Memory
Writing Flash Memory

This LED status indicates that the flash memory is being erased or
written when a flash memory writing tool was connected before
turning the power ON.

Lit

Lit

Flash Memory Write Completed
Normally

This LED status indicates that the flash memory was written
successfully when a flash memory writing tool was connected
before turning the power ON.

Lit

Blinking

Flash Memory Write Error

This LED status indicates that the flash memory write operation
failed (error end) when a flash memory writing tool was connected
before turning the power ON.
Either check the Module's ROM or turn the power OFF and then
ON to try writing again.

(cont’d)

Cl

as

si

ficati

on

LED Indicator

Indicator Details

Meaning

RUN

ERR

TX

Advertising